FAA-440 Analog Bases

FAA-440 Analog Bases
  • Modular design
  • Easy detector removal for cleaning and servicing
  • Stable mounting of detectors
  • Terminal screws for remote LED, Data In and Out provided
  • Some models include isolator circuitry which prevents the entire SLC loop from being disabled when a short circuit occurs
  • Overview
    Maximum current consumption at 77°F (25°C) and 39 V bus voltage
    Standby 0.07 mA
    Alarm 10 mA
    Operating voltage (SLC loop) 24 V DC to 41 V DC
    Internal resistance < 50 Ω
    Power up time < 30 ms
    Shut down time < 50 ms
    Protection category IP 42
    Relative Humidity < 95% (non‑condensing)
    Installation Temperature +32°F to +100°F (0°C to +38°C)
    Storage temperature -13°F to +176°F (-25°C to +80°C
    Dimensions
    Detector with 4-inch base 5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
    Detector with 6-inch base 7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
    Housing Material CYCOLOY/ABS

    Images

     
  • Certificates (3)
    Title Type Language
    UL PDF
    CSFM PDF
    Declaration of Conformity PDF
     
  • Documents (2)
    Title Type Language
    資料表 PDF
    安裝手冊 PDF
     
 

Product variants

FAA-440-B6 類比裝置標準型底座 6 吋

Standard 6-inch base. Used in combination with FAP-440 and FAH-440 detectors to provide early fire warning for life safety and property protection.

Commercial Type No.: FAA-440-B6
Product No.: F.01U.164.308