EMIL Expansion Modules LSN

EMIL Expansion Modules LSN
  • Connects to 6 detector zones (conventional detector or monitoring contact inputs), 4 free control outputs and to arming devices (e.g. NBS 10) with associated system components
  • Monitors the primary lines for alarms, short circuits or wire interruptions
  • Expanded system limiting values in the "improved version" LSNi mode
  • Tamper contact (tamper alarm) and integrated buzzer
  • Overview
    LSN part
    Minimum operating voltage in VDC 15
    Maximum operating voltage in VDC 33
    Maximum current consumption in mA 4.95
    Other expansion module functions
    Minimum operating voltage in VDC 9
    Maximum operating voltage in VDC 30
    Maximum current consumption in mA at 12 V 370
    Maximum current consumption in mA at 28 V 180
    External devices
    Minimum output voltage in VDC 11.9
    Maximum output voltage in VDC 16.3
    Maximum output current in mA 100
    Primary lines PL 1 - PL 6
    Connection options 6 detector zones can be programmed as hold-up, intrusion, tamper, closure, or entry
    Terminal resistance in kΩ 12.1
    Interruption voltage in V 6
    Maximum line resistance in Ω 100
    Alarm criteria ± 40% of terminal resistance
    Maximum response time in ms 200
    Control outputs S1 - S3
    Principle Open collector, 12 V when active, 0 V switching
    Maximum voltage in V 30
    Maximum switching voltage in V 1.4
    Maximum switching current in mA 20
    Control output S4
    Principle 12 V switching
    Minimum switching voltage in V 11.9
    Maximum switching voltage in V 16.3
    Maximum switching current in mA 100
    Primary lines PL 1 – PL 6
    Primary lines 1, 2, 5, 6 See PL 1 - PL 6 of table primary lines and control outputs
    Primary line PL 3 Block-type lock or code switching unit
    Primary line PL 4 Code switching unit
    End-of-line resistorsPrimary line PL 3 block type lock RE = 12.1 kΩ ±1% (armed) RE = 12.1 kΩ II 3.92 kΩ ±1% (unarmed)
    End-of-line resistors Primary line PL 3 or PL 4 coded arming device RE = 12.1 kΩ ±1% (coded arming device invalid) RE = 12.1 kΩ II 3.92 kΩ ±1% (coded arming device valid)
    S1–S3 control outputs
    Principle Open collector, 12 V when active, 0 V switching
    Maximum current in mA 20
    Maximum voltage in V 30
    Maximum witching voltage in V 1.4
    Maximum line resistance 2 x 10 Ω
    Short-circuit stability in s 2
    Control output S4 (block-type lock magnet)
    Maximum current in mA 100 mA
    Minimum voltage in V 11.9
    Maximum voltage in V 16.3
    Maximum line resistance 2 x 5 Ω
    Short-circuit stability in s 2
    Minimum operating temperature in °C 0
    Maximum operating temperature in °C 55
    Minimum storage temperature in °C -25
    Maximum storage temperature in °C 75
    Maximum relative humidity in % 93
    Protection class IP30
    Environmental class II
    EMC interference immunity EN 60950, EN 50130, VdS 2110
    EMC emitted interference EN 61000-6-3

    Images

     
  • Certificates (1)
    Title Type Language
    Declaration of Conformity PDF
     
  • Documents (4)
     
 

Product variants

ISP-PCBA-EMIL 嵌入式安裝 LSN 擴充模組

Flush-mounting version For connecting 6 detector zones, 4 control outputs or arming devices (e.g. NBS 10) to the local security network (LSN)

Commercial Type No.: ISP-PCBA-EMIL
Product No.: F.01U.078.200